The Watts 774DCDA-OSY-TS-GPM 12 is a 12" double check detector assembly (DCDA) with Flanged connections, approved for low health hazard protection. It features a stainless body. Rated to 175 psi and 33°F to 110°F.
This 12 inch double check detector backflow preventer assembly prevents the backflow of fire protection system substances from being pumped or siphoned into the potable water supply. It is designed for installation on applications identified by local authorities as non-health hazard, such as on fire protection systems. This assembly consists of a compact construction and short lay length, ideal for retrofit installations and can be installed in a horizontal or vertical flow-up position. It features a lightweight stainless steel body, thermoplastic and stainless steel check valves that provide low head loss. It has a gallons per minute meter, outside stem and yoke shutoffs, and tamper switch. The maximum working pressure is 175 psi (12.06 bar).
Features
- Includes UL-listed fire tamper supervisory switch
- Stainless steel for corrosion resistance
- Designed for minimum head loss
- 150 pound ANSI/AWWA CL D flanged
- Outside stem and yoke shutoffs
- Includes: Tamper Switch
Common Questions
- What hazard level is this DCDA approved for?
- It is rated for low health hazard (non-toxic, "pollutant") cross-connections only. Where the substance downstream could be a health hazard, codes require a reduced pressure zone (RPZ) assembly instead. The assembly is listed to ASSE 1048.
- Can this be installed on potable water?
- No. This model is not certified lead-free, so it may not be installed in potable water systems in states enforcing the NSF/ANSI 372 weighted-average lead rule. Use it on non-potable service — fire lines, irrigation or industrial water — or order the LF (lead-free) version of this model for drinking-water use.
- Does this assembly have to be tested every year?
- Yes. This is a field-testable assembly. Most water authorities require it to be tested and certified by a licensed backflow tester at installation and annually thereafter.
- What shutoff valves are included?
- It is supplied with outside screw and yoke (OS&Y) gate valves on the inlet and outlet. OS&Y gates give the visible open/shut indication that fire-line and many water-authority specs require.
- Is this suitable for a fire sprinkler line?
- Yes. Detector assemblies are built for fire sprinkler service: the metered bypass registers the low flows that reveal a leak or an unauthorized tap on the fire line. This model is UL Classified and FM Approved. The bypass meter reads in GPM.
- How does this have to be installed?
- It is approved for either horizontal or vertical installation, with the flow arrow on the body pointing in the direction of flow.
Specifications
-
Type: Double Check
-
Size: 12"
-
Inlet Size: 12"
-
Outlet Size: 12"
-
Connection: Flanged
-
Body Material: Stainless
-
Max Pressure (psi): 175
-
Application: Fire Protection
-
Backflow Protection: Backpressure
-
Operation: Continuous
-
Country of Origin: United States
-
Warranty: 1 Year Limited
-
MPN: 774DCDA-OSY-TS-GPM 12
-
Temperature: 33°F to 110°F
-
Certifications: CSA-B64, UL, FM
-
Lead-Free: No
-
Assembly Type: DCDA
-
Hazard Protection Level: Low Health Hazard
-
ASSE Standard: ASSE 1048
-
USC FCCCHR Approved: No
-
Fire Protection Listing: UL Classified;FM Approved
-
Field Testable: Yes
-
Shutoff Valves: OSY Gate
-
Approved Orientation: Horizontal & Vertical
-
Flood Sensor (SentryPlus Alert): No
-
Strainer Included: No
-
Air Gap Fitting Included: No
-
Bypass Meter: GPM