Specifications
Description
The Watts IDROSET CSD-125 is a 1-1/4" direct-reading balancing valve with NPT connections. It features a brass and polyamide body and a epdm seat.
This 1 1/4 inch calibrated flow measurement and balancing valve monitors system flow in low to medium flow rate HVAC units, providing highly accurate flow measurement and adjustment. It consists of a brass and polyamide body with F-NPT connections, integral patented technology that allows the reading and setting of flow rate without the need for instrumentation or tools. It is equipped with a GPM gauge to read flow and a hand wheel to set and lock the flow setting. Its ball valve construction allows full shut-off capability and is ideal in hot/chilled water units such as fan coil units, water source heat pumps, reheat coils, panel coils, small branch lines, unit heaters, unit ventilators, finned radiation and convectors.
Features
- Integral flow measurement technology
- GPM gauge for reading flow
- Hand wheel for setting flow
- Positive shut-off
Common Questions
- Do I need a separate meter to read the flow?
- No. The IDROSET CSD-125 reads flow directly. It has an integral GPM dial, factory-calibrated to +/-10%, so you turn the handwheel until the dial shows the design flow and lock it there. No differential-pressure meter, no hoses, no flow-chart lookup, and no second trip to the mechanical room. It holds that accuracy across a 25:1 turndown.
- Can it also shut off the circuit?
- Yes. The IDROSET CSD-125 gives positive, drip-tight shutoff, so it doubles as the service valve for the circuit and you do not have to buy and install a separate ball valve next to it. The memory stop preserves your balanced setting: close the valve for service, reopen it against the stop, and the circuit returns to the same flow without rebalancing.
- Can I use it on a domestic hot water recirculation line?
- No. The IDROSET CSD-125 is not a lead-free model, so it is restricted to closed hydronic heating and chilled-water loops and other non-potable service. For DHW recirculation balancing, choose the lead-free equivalent — the Watts LFCSM-61-S (PT-port) or LFiDROSET CSD (direct-reading).
Specifications
- Type: Balancing
- Size: 1-1/4"
- Inlet Size: 1-1/4"
- Outlet Size: 1-1/4"
- Connection: NPT
- Body Material: Brass and Polyamide
- Seat / Seal Material: EPDM
- Application: Hydronic Heating/Cooling
- Country of Origin: Italy
- Warranty: 1 Year Limited
- MPN: IDROSET CSD-125
- Lead-Free: No
- Balancing Type: Direct-Reading
- Valve Functions: Balancing;Flow Measurement;Shutoff
- Flow Readout: Integral direct-reading GPM dial — no separate meter required
- Memory Stop: Yes
- Positive Shutoff: Yes
- Flow Accuracy (+/- %): 10
- Turndown Ratio: 25:1
Product Information
Dimensions
| Size Nominal | 1-1/4" | Inlet Size | 1-1/4" |
| Outlet Size | 1-1/4" | End Connection | NPT |
Details
| Series | iDROSET CSD | Device Type | Balancing |
| Body Material | Brass and Polyamide | Seat Material | EPDM |
| Application | Hydronic Heating/Cooling | Balancing Type | Direct-Reading |
| Functions | Balancing, Flow Measurement, Shutoff | Readout Ports | Integral direct-reading GPM dial — no separate meter required |
| Memory Stop | Yes | Positive Shutoff | Yes |
| Accuracy % | 10.0 | Turndown Ratio | 25:1 |
Recommended Products
Recently Viewed
What Our Customers Say
-
The best
Is ray -
A beautiful and smart woman with a helpful heart that is a surprise to find in a plumbing supply co., Nekell.
-
Ray Rhodes thanks for your help. 5 star service at City Supply.
-
Excellent service
-
Excellent
-
Got me flushing again
-
Needed a faucet quick. They had what we needed within 5 minutes and were all so nice
-
Excellent service as always. All the stuff I needed. Thanks Julio.
-
absolutely the most helpful gracious and polite people I have dealt with in a very long time. thank you so much!!
-
Material Always on Hand or Quick order
-
Excellent service and help from the staff who work at this place
-
Excellent service and attention, everyone was very friendly. 5 stars for Mr. Julio.