{"product_id":"zurn-34-zw1017xlc","title":"Zurn 34-ZW1017XLC 3\/4\" Lead-Free Aqua-Gard® Thermostatic Mixing Valve - Point of Source (ASSE 1017)","description":"\u003cp\u003eThe Zurn Wilkins 34-ZW1017XLC is a 3\/4\" lead-free point-of-distribution (master) thermostatic mixing valve with Sweat connections. It blends hot and cold water to a field-set outlet temperature of 95°F to 131°F. It is listed to ASSE-1017. It features a lead-free bronze body. Rated to 145 psi. This model is certified lead-free for potable-water installations.\u003c\/p\u003e\u003cp\u003eThe ZW1017XL Aqua-Gard® Thermostatic Mixing Valve is utilized in both residential and most light commercial point-of-use installations to mix hot and cold water and reduce the hot water temperature in the distribution system to 122°F (50°C) or less. The ZW1017XL valve is suitable for installation in areas inaccessible to end users at the hot water source, and is recommended to be installed with a shut-off valve and thermometer in the tempered water line for safety and accuracy in conjunction with the ASSE 1070 device. Included with both inlet strainers and check valves, the ZW1017XL can also be installed in any position.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eFeatures\u003c\/strong\u003e\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eInstalls at the potable water heat source and can be oriented either vertically or horizontally for added versatility\u003c\/li\u003e\n\u003cli\u003eEfficiently reduces hot water temperature to 122°F or less\u003c\/li\u003e\n\u003cli\u003eHigh protection from scalding injuries\u003c\/li\u003e\n\u003cli\u003eCheck valves and inlet strainers included for added convenience\u003c\/li\u003e\n\u003cli\u003eLow-lead law compliant\u003c\/li\u003e\n\u003cli\u003eASSE® Listed 1017\u003c\/li\u003e\n\u003cli\u003eIAPMO® Listed\u003c\/li\u003e\n\u003cli\u003eCSA® Certified\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003e\u003cstrong\u003eCommon Questions\u003c\/strong\u003e\u003c\/p\u003e\u003cdl\u003e\n\u003cdt\u003e\u003cstrong\u003eCan I install this at a lavatory or sink?\u003c\/strong\u003e\u003c\/dt\u003e\n\u003cdd\u003eNo. This valve is listed to ASSE 1017 only, a point-of-distribution standard: it tempers water leaving the water heater for the building distribution piping and should never deliver water directly to a user. Install an ASSE 1070 listed valve downstream at each fixture.\u003c\/dd\u003e\n\u003cdt\u003e\u003cstrong\u003eDoes the hot and cold supply pressure matter?\u003c\/strong\u003e\u003c\/dt\u003e\n\u003cdd\u003eYes - the maximum allowed pressure differential between the hot and cold inlets is 15 psi. A bigger imbalance than that is a real install-failure mode: the valve cannot hold its set temperature if one side is starved relative to the other.\u003c\/dd\u003e\n\u003cdt\u003e\u003cstrong\u003eDoes it have integral checks?\u003c\/strong\u003e\u003c\/dt\u003e\n\u003cdd\u003eYes. Check valves and strainer screens are built into the hot and cold inlets to stop cross-flow between the supplies and keep debris off the thermostat.\u003c\/dd\u003e\n\u003c\/dl\u003e\u003cp\u003e\u003cstrong\u003eSpecifications\u003c\/strong\u003e\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eType:\u003c\/strong\u003e Aqua-Gard® Thermostatic Mixing Valve - Point of Source (ASSE 1017)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSize:\u003c\/strong\u003e 3\/4\"\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInlet Size:\u003c\/strong\u003e 3\/4\"\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOutlet Size:\u003c\/strong\u003e 3\/4\"\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eConnection:\u003c\/strong\u003e Sweat\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eBody Material:\u003c\/strong\u003e Lead-Free Bronze\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMax Pressure (psi):\u003c\/strong\u003e 145\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eApplication:\u003c\/strong\u003e Domestic Water\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMPN:\u003c\/strong\u003e 34-ZW1017XLC\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCertifications:\u003c\/strong\u003e ASSE-1017, IAPMO, CSA B125.3, NSF\/ANSI\/CAN 61-9\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eLead-Free:\u003c\/strong\u003e Yes\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eASSE Listing:\u003c\/strong\u003e ASSE-1017\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInstall Point:\u003c\/strong\u003e Point of Distribution\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOutlet Temp — Min (°F):\u003c\/strong\u003e 95\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOutlet Temp — Max (°F):\u003c\/strong\u003e 131\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMax Hot Inlet Temp (°F):\u003c\/strong\u003e 195\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMinimum Controllable Flow (gpm):\u003c\/strong\u003e 0.5\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMaximum Flow (gpm):\u003c\/strong\u003e 18.0\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eIntegral Checks \u0026amp; Filter Screens:\u003c\/strong\u003e Yes\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMax Hot\/Cold Pressure Differential (psi):\u003c\/strong\u003e 15\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Zurn","offers":[{"title":"Default Title","offer_id":55656990114091,"sku":"34-ZW1017XLC","price":321.99,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0277\/3168\/9577\/files\/ZW1017XLHT_cdabd60e-9e8c-44de-b903-ddf46f475b74.jpg?v=1790047842","url":"https:\/\/citysupplygroup.com\/products\/zurn-34-zw1017xlc","provider":"City Supply","version":"1.0","type":"link"}