{"product_id":"zurn-12in-350","title":"Zurn 12IN-350, Ductile Iron, Flanged","description":"\u003cp\u003eThe Zurn Wilkins 12IN-350 is a 12\" double check valve assembly with Flanged connections, approved for low health hazard protection. It features a ductile iron body. Rated to 175 psi and up to 140°F.\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eCommon Questions\u003c\/strong\u003e\u003c\/p\u003e\u003cdl\u003e\n\u003cdt\u003e\u003cstrong\u003eWhat hazard level is this Double Check approved for?\u003c\/strong\u003e\u003c\/dt\u003e\n\u003cdd\u003eIt is rated for low health hazard (non-toxic, \"pollutant\") cross-connections only. Where the downstream substance could be a health hazard, codes require a reduced pressure zone (RPZ) assembly or a detector assembly instead. The assembly is listed to ASSE 1015.\u003c\/dd\u003e\n\u003cdt\u003e\u003cstrong\u003eDoes this assembly have to be tested every year?\u003c\/strong\u003e\u003c\/dt\u003e\n\u003cdd\u003eYes. This is a field-testable assembly with 4 test cocks. Most water authorities require it to be tested and certified by a licensed backflow tester at installation and annually thereafter. It carries USC FCCCHR approval, which many jurisdictions accept as their sole approval list.\u003c\/dd\u003e\n\u003cdt\u003e\u003cstrong\u003eWhat shutoff valves are included?\u003c\/strong\u003e\u003c\/dt\u003e\n\u003cdd\u003eIt is supplied with non-rising stem (NRS) resilient-seated gate valves on the inlet and outlet.\u003c\/dd\u003e\n\u003cdt\u003e\u003cstrong\u003eIs this listed for fire protection service?\u003c\/strong\u003e\u003c\/dt\u003e\n\u003cdd\u003eYes -- it is UL Classified and C-UL Classified and FM Approved, the listings normally required for a backflow device on a fire sprinkler supply.\u003c\/dd\u003e\n\u003c\/dl\u003e\u003cp\u003e\u003cstrong\u003eSpecifications\u003c\/strong\u003e\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eSize:\u003c\/strong\u003e 12\"\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eConnection:\u003c\/strong\u003e Flanged\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eBody Material:\u003c\/strong\u003e Ductile Iron\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMax Pressure (psi):\u003c\/strong\u003e 175\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eApplication:\u003c\/strong\u003e Domestic Water\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eBackflow Protection:\u003c\/strong\u003e Both\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMPN:\u003c\/strong\u003e 12IN-350\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTemperature:\u003c\/strong\u003e up to 140°F\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCertifications:\u003c\/strong\u003e ASSE-1015, AWWA-C510, AWWA-C606, CSA-B64.5, C-UL, UL, FM, USC, NSF-61, NSF-372, IAPMO\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eAssembly Type:\u003c\/strong\u003e Double Check\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHazard Protection Level:\u003c\/strong\u003e Low Health Hazard\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eASSE Standard:\u003c\/strong\u003e ASSE 1015\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eUSC FCCCHR Approved:\u003c\/strong\u003e Yes\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eFire Protection Listing:\u003c\/strong\u003e UL Classified;C-UL Classified;FM Approved\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eField Testable:\u003c\/strong\u003e Yes\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eNumber of Test Cocks:\u003c\/strong\u003e 4\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eShutoff Valves:\u003c\/strong\u003e NRS Gate\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Zurn","offers":[{"title":"Default Title","offer_id":55656160264491,"sku":"12IN-350","price":45028.99,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0277\/3168\/9577\/files\/OIP_0cbf89b4-28ab-4e51-8756-a7f915e8e70f.jpg?v=1792594881","url":"https:\/\/citysupplygroup.com\/products\/zurn-12in-350","provider":"City Supply","version":"1.0","type":"link"}